• <tr id='wh6em6'><strong id='wh6em6'></strong><small id='wh6em6'></small><button id='wh6em6'></button><li id='wh6em6'><noscript id='wh6em6'><big id='wh6em6'></big><dt id='wh6em6'></dt></noscript></li></tr><ol id='wh6em6'><option id='wh6em6'><table id='wh6em6'><blockquote id='wh6em6'><tbody id='wh6em6'></tbody></blockquote></table></option></ol><u id='wh6em6'></u><kbd id='wh6em6'><kbd id='wh6em6'></kbd></kbd>

    <code id='wh6em6'><strong id='wh6em6'></strong></code>

    <fieldset id='wh6em6'></fieldset>
          <span id='wh6em6'></span>

              <ins id='wh6em6'></ins>
              <acronym id='wh6em6'><em id='wh6em6'></em><td id='wh6em6'><div id='wh6em6'></div></td></acronym><address id='wh6em6'><big id='wh6em6'><big id='wh6em6'></big><legend id='wh6em6'></legend></big></address>

              <i id='wh6em6'><div id='wh6em6'><ins id='wh6em6'></ins></div></i>
              <i id='wh6em6'></i>
            1. <dl id='wh6em6'></dl>
              1. <blockquote id='wh6em6'><q id='wh6em6'><noscript id='wh6em6'></noscript><dt id='wh6em6'></dt></q></blockquote><noframes id='wh6em6'><i id='wh6em6'></i>
                欢迎来到电力微机保护网
                打开客服菜单
                杭州继保南瑞公司
                contact us

                联系我们

                联系我们
                继保南瑞微机保护 > 产品说明书 > 9666 PT并列保护测控装置说明书
                9666 PT并列保护测控装置说明书
                编辑 :

                专注微机保护

                时间 : 2020-05-18 05:50 浏览量 : 391

                PT并列保护测控装置说明书

                1 概述

                1.1 适用范围

                9666 适用于110KV以下电压等级的双母线PT的测量、保护、并可实现同等电压的两段PT并列,可组屏安装,也可在开关柜就地安装。

                1.2 保护特点

                人性化设计界面:大屏幕液晶显示屏,实时显示电流、电压、功率、频率等电气量,汉化操作菜单简单易用,清晰显示保护动作全过程,使动作过程透明。

                采样性能优越:保护电路和测量电路具有独立的采样回路,既保证了监测精度,又保证了保护的抗饱和性能。

                出口独立:所有出口继电器都单独使用一个通道,方便保护的投入和退出。遥控分合、保护跳闸、事故信号、预告信号及其他特殊信号出口都可单独配置。

                自保功能强:每个断路器对应一个操作回路,紧急时可直接对开关进行操作;另外,装置具有断路器跳合闸线圈保护功能,避免因机械拒动而烧毁断路器线圈。

                替代性强:保护装置功能强大,具有“四遥”功能,完全可替代常规继电器的保护,全嵌入式的数字化平台结构,大大减少了维护量。

                设计灵活:根据现场情况,可设计成集中组屏式,也可分散安装于开关柜。

                运行可靠:完善的自检体系,硬件检测直到继电器跳闸出口,均采用可靠的元器件。

                1.3 保护配置

                1.3.1 保护配置

                I母、II母过电压          (告警)

                I母、II母低电压          (告警)

                I母、II母PT断线         (告警)

                I母、II母PT失压         (告警)

                I母、II母母线绝缘监测    (告警)

                PT并列                  (带重动出口)

                1.3.2 测控功能

                母线电压:Uab1、Ubc1、Uca1、Ua1、Ub1、Uc1;

                Uab2、Ubc2、Uca2、Ua2、Ub2、Uc2;

                频率:f;

                具有14路遥信开入采集;

                6路并列出口、2路信号出口(告警/跳闸各1个);自带1路装置失电信号;

                事件SOE记录;

                1.3.3 通信功能

                通讯接口:

                1路以太网口

                1路485口

                1路B码对时口(也可作为第2路485通讯口)

                通讯规约:继保南瑞-103通讯规约,MODBUS RTU规约。

                1.3.4 GPS对时功能

                支持IRIG-B对时。

                1.3.5保护信息功能

                装置描述的远方查看。

                设备参数定值的远方查看。

                保护定值和区号的远方查看、修改功能。

                软压板状态的远方查看、遥控和就地投退功能。

                装置保护开入状态的远方查看。

                装置运行状态(包括保护动作元件的状态和自检报警信息等)的远方查看。

                远方对装置信号复归。

                2 技术参数

                2.1 环境参数

                正常工作温度:  -10 ~ 55 ℃

                极限工作温度:  -20 ~ 60 ℃

                贮存及运输:    -30 ~ 70 ℃

                大气压力:          60 ~ 110 Kpa

                2.2 额定电气参数

                频率:              50Hz

                交流电压:100V或57.7V(额定电压UN)

                交直流工作电源:交流:AC85V~265V;50Hz±0.5Hz;谐波畸变率不大于15%

                直流:DC85V~265V,纹波系数不大于5%

                数字系统工作电压:+5V,允许偏差:±0.15V

                继电器回路工作电压:+24V,允许偏差:±2V

                功耗:

                交流电压回路:UN = 57.7V,每相不大于0.5VA

                直流电源回路:  正常工作时,不大于15W

                保护动作时,不大于25W

                保护回路过载能力:

                交流电压回路:1.2倍额定电压,连续工作

                直流电源回路:  80 ~ 115% 额定电压,连续工作

                装置经受上述的过载电流/电压后,绝缘性能不下降。

                2.3 主要技术指标

                定值精度

                频率定值误差:    ≤±0.01Hz

                激励量≥1.2倍定值时,瞬时动作段动作时间:≤35ms

                延时动作段动作时间离散误差:≤30ms

                各保护段返回时间:≤25ms

                遥测量计量等级

                频率:               ±0.01Hz

                其他:               0.5级

                遥信量分辨率:       小于1ms

                工作电压: DC220V/DC24V;(DC220V订货需注明,默认是DC24V)

                输入方式:有源接点或无源接点;(默认是无源接点)

                开关量输出

                输出形式:无源接点;

                冲击过流能力:6A@3s;15A@0.5s;30A@0.2s ;

                动作时间:<8ms;

                返回时间:<5ms;

                电磁兼容

                静电放电:            符合GB/T14598.14-1998  3级

                辐射电磁场干扰:      符合GB/T14598.9-2002   3级

                快速瞬变干扰:        符合GB/T14598.10-2007   B级

                1MHz脉冲群干扰:    符合 GB/T14598.13-2008   3级

                浪涌抗扰度:          符合GB/T14598.18-2001  3级

                绝缘试验

                装置绝缘耐压、耐湿热、抗振动、抗冲击、抗碰撞性能符合国际GB/T7261-2000的有关标准(绝缘≥20MΩ)。

                3 保护菜单说明

                3.1 保护投退菜单

                保护序号

                代号

                整定方式

                备注

                01

                RLP01

                I母过电压

                /退

                告警

                02

                RLP02

                I母低电压

                /退

                告警

                03

                RLP03

                IPT断线

                /退

                告警

                04

                RLP04

                IPT失压

                /退

                告警

                05

                RLP05

                I母绝缘监测

                /退

                告警

                06

                RLP06

                II母过电压

                /退

                告警

                07

                RLP07

                II母低电压

                /退

                告警

                08

                RLP08

                IIPT断线

                /退

                告警

                09

                RLP09

                IIPT失压

                /退

                告警

                10

                RLP10

                II母绝缘监测

                /退


                11

                RLP11

                PT并列

                /退


                定值序号

                代号

                     

                整定菜单

                整定值说明

                00


                保护定值套数

                1~3


                01

                Kv1

                IPT变比/10

                0.01~300.00

                整定电压等级值,10kV整定为10

                02

                Udz1

                I母过电压定值

                50~200V


                03

                Tuzd1

                I母过电压延时

                0~100s


                04

                Udz2

                I母低电压定值

                30~100V


                05

                Tuzd2

                I母低电压延时

                0~100s


                06

                Upt1

                IPT断线定值

                10~90V


                07

                Tupt1

                IPT断线延时

                0~100s


                08

                Upt2

                IPT失压定值

                0.1~60V


                09

                Tupt2

                IPT失压延时

                0~100s


                10

                U0dz1

                I母绝缘监测定值

                0.1~100V


                11

                Tu0zd1

                I母绝缘监测延时

                0~100s


                12

                Kv2

                IIPT变比/10

                0.01~300.00

                整定电压等级值,10kV整定为10

                13

                Udz3

                II母过电压定值

                50~200V


                14

                Tuzd3

                II母过电压延时

                0~100s


                15

                Udz4

                II母低电压定值

                30~100V


                16

                Tuzd4

                II母低电压延时

                0~100s


                17

                Upt3

                IIPT断线定值

                10~90V


                18

                Tupt3

                IIPT断线延时

                0~100s


                19

                Upt4

                IIPT失压定值

                0.1~60V


                20

                Tupt4

                IIPT失压延时

                0~100s


                21

                Uu0dz2

                II母绝缘监测定值

                0.1~100V


                22

                Tu0zd2

                II母绝缘监测延时

                0~100s


                装置端子图说明

                交流回路

                控制回路

                通讯回路

                端子

                定义

                说明

                端子

                定义

                说明

                端子

                说明

                端子

                说明

                Z1

                Ua1*

                母线

                电压

                F1

                Un1

                母线

                电压

                P1

                工作正电源

                T1

                485A

                Z2

                Ub1*

                F2

                Un1

                P2

                工作负电源

                T2

                485B

                Z3

                Uc1*

                F3

                Un1

                P3

                装置接地

                T3

                IRIG-B+

                Z4

                u01*

                零序

                F4

                u01

                电压

                P4


                T4

                IRIG-B-

                Z5



                F5



                P5


                T5

                备用

                Z6

                Ua2*

                母线

                电压

                F6

                Un2

                母线

                电压

                P6


                T6

                备用

                Z7

                Ub2*

                F7

                Un2

                P7


                T7

                装置失电

                (常闭点输出)

                Z8

                Uc2*

                F8

                Un2

                P8


                T8

                Z9

                u02*

                零序

                F9

                u02

                电压

                P9


                Z10



                F10



                P10


                Z11



                F11



                继电器出口

                开入量采集

                Z12



                F12



                装置接线说明

                端子

                说明

                端子

                说明

                1.以上接线为标准的接线方式;

                2.若电压采用V-V接线,则Ua1*Z1Ub1*F1Uc1*Z2即可。Ua2*Z6Ub1*F6Uc2*Z7即可。

                3U01U02为开口三角电压,任何一段母线PT只有一个(Y-Y开口接法才有)。

                4.  若保护装置使用交流供电,则P1接火线,P2接零线。

                 

                C1

                并列信号出口

                R1

                1#PT合位

                C2

                告警信号端

                R2

                2#PT合位

                C3

                信号公共端

                R3

                备用开入量

                C4

                备用出口

                R4

                PT并列允许

                C5

                备用出口

                R5

                备用开入量

                C6

                公共端

                R6

                备用开入量

                C7

                IUA输入

                R7

                备用开入量

                C8

                IUA输出

                R8

                备用开入量

                C9

                IIUA输入

                R9

                备用开入量

                C10

                IIUA输出

                R10

                备用开入量

                C11

                IUB输入

                R11

                备用开入量

                C12

                IUB输出

                R12

                备用开入量

                C13

                IIUB输入

                R13

                备用开入量

                C14

                IIUB输出

                R14

                备用开入量

                C15

                IUC输入

                R15

                开入内供正电

                C16

                IUC输出

                R16

                开入量公共端

                C17

                IIUC输入


                C18

                IIUC输出


                备注:详细说明书请与公司联系

                文章来自电力微机保护网


                产品咨询电话号码:13655813266 手机号码微信同步,欢迎咨询!

                热门推荐:

                no cache
                Processed in 0.807347 Second.